Release Notes for Partners

This website contains an overview of all software updates published by sonnen for all sonnenBatteries for generation 8 or higher. This page is only designed for our partners, installers, and service partners. If you intend to share release notes with your customers please refer to this page here.

Note:

Please note that the sonnenBatterie will automatically download and install any new software updates if you are connected to the Internet. No further action is necessary on your part. sonnen may delay the download and update of specific software releases up to 14 days.

Also note that the eclipse is not illuminated during the software update and your system will not be available via the app or the web portal. To ensure that the update can be successfully installed, the storage system must not be switched off, restarted or disconnected from the internet during the update. We therefore ask you to wait at least 15 minutes before restarting your storage system or contacting our customer service if the eclipse is not illuminated.

If the system is offline for more than 8 weeks, please establish a connection to the Internet so that your system can download and install available updates. If you only want to download and install mandatory updates, please contact our customer service.

 

Software version: 1.14.5

Release date: August 19th, 2024
Installation mandatory: Yes

Features:

  • [All Products] With this software, we introduce a new feature called ‘Surplus Fullcharge’. When this feature is activated, and if the battery needs a full charge for battery care reasons, it will only charge from the PV generation to further optimise PV self-consumption. The battery will not draw any energy from the grid to cater the full charge. Be aware that the full charge will not be suspended until 100% State of Charge is reached. For the battery behaviour this means that the full charge can take significantly longer when this feature is enabled compared to full charge from grid. This feature can be enabled by the user from the Dashboard as shown below (disabled by default).
  • More information on battery maintenance can be found in our blog article: https://sonnengroup.com/battery-maintenance/
Software version: 1.14.5 notes

Bugfixes:

  • [All Products] In some rare cases the sonnenBatterie was interfering with the detection of other connected devices in the local network. This issue is now fixed. 
  • [All Products] All systems are showing the correct local time zone in the Dashboard now.
  • [sonnenModule 4 based systems] This version is including a new sonnenModule 4 firmware version to fix an error on battery module level and improves the startup of the battery modules. It is recommended to run this firmware update during commissioning.

 

Software version: 1.13.4

Release date: April 17th, 2024
Status: Stable

FEATURE:

  • [Italian systems] A self-test can be re-executed by the installer if a previous self-test has failed.
  • [Global system fleet] Power meter setup in the Commissioning Assistant as well as in the Dashboard self-adjusts based on changing screen sizes. Also, the selection of the power meter setting is more user-friendly.

Large screen size:

Software version: 1.13.4 - Power Meter

 

Small (minimised) screen size:

Software version: 1.13.4 - Power Meter small screen

 

  • [sonnenCore+, sonnenEvo] It is possible for the installers and service users to successfully set the UL 1741 SB grid code parameters in the Commissioning Assistant.

 

Bugfixes:

  • [Italian Systems] ‘Segnale Esterno OFF’ grid codes are removed from the Commissioning Assistant grid code list to present clearer options to our installers.
  • [ecoLinx 1.5] Systems with an active VPP status respect the backup buffer when the State of Charge is less than the minimum State of Charge set for the VPP.
  • [US system fleet] High frequency AXS port logging is disabled from this software version to prevent SD card corruption.
  • [US eco and ecoLinx] External generator now function during grid outage events with both sonnen eco & ecoLinx.
  • [sonnenModule 4 based systems] This version includes a new sonnenModule 4 firmware version to fix an error on battery module level. This new firmware improves the performance of the battery modules and prevents it from going into critical error unnecessarily. This firmware version is available as an update during the commissioning.

Software version: 1.12.5

Release date: February 5th, 2024
Status: Stable

FEATURE:

  • [sonnenBatterie 10, sonnenBatterie hybrid 9.53] It is now clear in the Commissioning Assistant that the installer can run the self-test only once the Italian grid-code is selected. 
  • [sonnenEvo] Ongrid stacking is made possible for sonnenEvo.

 

BUGFIX:

  • [sonnenBatterie 10 performance, sonnenProtect 8000] If an overload is caused by high reactive power, the system is no longer switched off completely but indicates overload by an orange flashing sonnen Eclipse.
  • [Global system fleet] This software version has enhancements to the battery management and inverter firmware update processes in the Commissioning Assistant.
  • [eco, ecolinx] The systems with the ‘Backup-Power USA’ mode will stay full charge and will not discharge. The systems will no longer switch operational mode to self-consumption mode.
  • [sonnenBatterie 10 perforamnce, sonnenProtect 8000] When an overload event occurs, the system will now recover only after manually switching the button on sonnenProtect 8000. 

 

Software version: 1.11.9

Release date: November 16th, 2023
Status: Stable

FEATURE:

  • [sonnenCore+, sonnenEvo] All required grid functions for the UL1741 SB regulations are now available after selecting this grid code via the Commissioning Assistant.
  • [sonnenCore+, sonnenEvo, eco, ecolinx] All four required CRD/PCS modes are now available for selection for any systems installed with the USA address.
  • [sonnenCore+, sonnenEvo] Users can now see that the system is CRD compliant along with the “CRD version,” in accordance with the UL 1741 standard within the Dashboard.
  • [Global system fleet] Two new backup buffer “recharge strategy” options are now available in the commissioning assistant and dashboard.
  1. Green charging: Only charge from excess PV or generator until the backup buffer is reached.
  2. Economical charging: (existing/default) Charge at a minimum power until the backup buffer, supplemental grid charging is permitted.
  3. Fast charging: Charge at up to max power until the backup buffer is reached, supplemental grid charging is permitted.
  • [sonnenCore+, sonnenEvo] When a RCMU is activated in a system, installers and service users can eliminate the cause of the error. Then they can access a button in the Dashboard Inverter Vendor Interface, allowing the RCMU error flag to be cleared and the system begins normal operation.
  • [sonnenBatterie hybrid 9.53, eco 8.03, hybrid 8.13, eco 9.43] It is now possible to update the sonnenModule 2 battery firmware remotely.
  • [Global system fleet] For troubleshooting purposes, individual sonnenModule 4 battery modules can now be identified.

 

BUGFIX:

  • [Global system fleet] The imprint “contact details” has been updated in the Commissioning Assistant and Dashboard.
  • [eco, ecoLinx] The systems will no longer switch operational modes from backup-power to self-consumption without user input.
  • [sonnenBatterie 10 performance] The system will now discharge at the full marketed power limit.
  • [sonnenBatterie 10] Improved inverter start-up sequence, avoiding loops and improving reliability.
  • [sonnenBatterie 10, eco 8, sonnenBatterie hybrid 9.53] The system will now correctly adhere to the household fuse limit while charging from surplus PV and/or grid power.
  • [Global system fleet] Improved accuracy in the portal for production and consumption values when in manual or automatic standby mode.
  • [sonnenBatterie10 performance, sonnenBatterie10, sonnenCore+, sonnenEvo, sonnenBatterie Evo] The installer can now successfully update the sonnenModulen 4 module firmware in the commissioning assistant.

 

Software Version: 1.10.7

Release date: August 21st, 2023
Status: Stable

BUGFIX:

  • [sonnenBatterie 10 performance] The issue of the system not charging from the excessive available PV due to the wrong household fuse limit calculation is solved. With this software, the system will respect the set household fuse limit (service entrance rating current) and accordingly charge the system and/or feed-in the grid.
  • [sonnenBatterie hybrid 9.53] Partners can now set or edit the Time-of-Use settings in the Partner Portal.
     

Software Version: 1.10.6

Release date: July 5th, 2023
Installation Mandatory: Yes

FEATURE:

  • sonnenBatterie Evo: Installers are able to set the 14/Australia power setting for Ingeteam inverter-based systems during the commissioning assistant in Australia.
  • sonnenBatterie 10: Italian grid codes are updated to reflect new standards: ‘Italy CEI 0-21 2016 segnale esterno on’ and ‘Italy CEI 0-21 2016 segnale esterno off’ are removed for more simplicity. ‘Italy CEI 0-21 2019 segnale esterno on’ and ‘Italy CEI 0-21 2019 segnale esterno off’ are replaced by ‘Italy CEI 0-21 2022 segnale esterno on’ and ‘Italy CEI 0-21 2022 segnale esterno off’.
  • sonnenBatterie hybrid 9.53: The two Italian grid codes “CEI 0-21 2019” have been replaced by “CEI 0-21:2022” as the grid code standard was updated.
  • sonnenBatterie 10 performance: When the sonnenBatterie 10 performance has the inverter with a monitor version format of 6XXXX, an ‘update inverter firmware’ button will be displayed in the dashboard. When this button is clicked by an installer or sonnen service, the inverter firmware update process will start, and the progress of the update will be displayed in the dashboard.
  • sonnenCore+, sonnenEvo, sonnenBatterie Evo: Updates global inverter firmware version to 1.12 for all countries and grid codes: Installers can update the inverter firmware directly via the commissioning assistant.
  • sonnenBatterie 10 performance: Service Entrance Rating (household fuse limit) on each phase of grid connection now being respected for standard and stacked systems, to prevent tripping during Full-Charge events for battery maintenance. The entered value must be understood as the total value for all three phases. Internally this value is divided by 3 and used as the limit for each phase.

 

BUGFIX:

  • sonnenProtect 4000: sonnenBatterie 10 works in backup mode with sonnenProtect 4000 using only one sonnenModule 4 battery module.
  • eco, ecoLinx, sonnenBatterie hybrid 8.13 & 9.53: sonnenModule 2-based systems will now show correct individual module data (cell voltage, cell temperatures, serial number, etc) in the dashboard.
  • Customers can now view their complete system history in the portal without any data gaps in the graph.
  • ‘System selection’ of the first page of the commissioning assistant is translated correctly into the Italian language.
  • sonnenBatterie Evo: Installers can set and change the connection/reconnection parameters for systems during the commissioning.
  • sonnenCore+, sonnenEvo, sonnenBatterie Evo: The inverter update process will now show the latest status including a number of retries in the commissioning assistant.
  • sonnenBatterie Evo, sonnenEvo, sonnenCore+: While off-grid, when the SOC reaches the upper state of charge limit, the system's frequency will now shift and disconnect the PV inverter to avoid overcharge. Once the battery is discharged again to the lower state of charge limit, the PV inverter will reconnect automatically.
  • The system will no longer unnecessarily activate a Full-Charge in cascade systems.

Software version: 1.9.4 Update

Release date: March 30th, 2023
Status: Stable

FEATURE:

  • sonnenCore+ stacking: First time supporting on-grid stacking for up to 3 systems allowing expansion of systems.
  • sonnenCore+ stacking: During the commissioning assistant, the necessity to update the FW of the inverter has been made clearer.

 

BUGFIX:

  • sonnenCore+ stacking: The backup buffer of the secondary system is now synchronized to the value of the primary system after reconnection.
  • sonnenCore+ stacking: During commissioning, the update of the inverter firmware is now always successful.
  • sonnenBatterie EVO: Back-up functionality has been improved and it is working as expected during off-grid conditions.
  • sonnenBatterie EVO: Over-discharge issue is resolved and the system discharges according to the actual load consumptions.

Software version: 1.9.4

Release date: March 30th, 2023
Status: Stable

FEATURE:

  • Grid code Sweden added to sonnenBatterie 10 performance
  • Input validation has been added for entered PV size value in Commissioning Assistant for avoiding unplausible PV size information.
  • Easier to recognize wrong power metering configuration: Show ERROR instead of 0W if a configured metering device is not working or present
  • New starting page for Commissioning Assistant 2.0: more user-friendly and understandable initial options for choosing single or cascade system.
     

BUGFIX:

  • Self-Consumption Relay works normally as per the set threshold power and holding time.
  • Improvement of sonnenBatterie 10 performance stability leads to correct data visualization of the state of charge on the customer portal, thus avoiding to show false sudden drops or jumps.
  • In sonnenBatterie 10 performance, offgrid switching after the grid reconnection is correctly shown on the eclipse and the dashboard.
     

Software version: 1.8.8 

Release date: February 13th, 2023 - only for new produced sonnenBatterie 10 performance 
Status: Stable 

FEATURE:  

  • sonnenBatterie 10 performance:  
    New firmware version of the internal inverter. No changes in functionality. 
     

Software version: 1.8.7

Release date: December 7th, 2022 
Status: Stable

FEATURE: 

  • Grid code sonnenBatterie 10 Italy: Additional Italian grid codes are now available for the sonnenBatterie 10. They correspond to the CEI 0-21:2022 Class B standard (systems > 11.08 kW) and are called: Italy CEI 0-21:2022 >11.08 kW segnale esterno on, Italy CEI 0-21:2022 >11.08 kW segnale esterno off 
  • In addition, the previous grid codes for Class A have been updated from CEI 0-21:2019 to CEI 0-21:2022.
Inverter Setting
  • Dashboard 2.0 and Commissioning Assistant 2.0: Spanish is now available as an additional language. 
  • sonnenBatterie hybrid 9.53: For more clarity, only those countries for which a grid code is available are now available in the selection list of the Commissioning Assistant 2.0.  
  • API V2: New data points for requesting battery module data and inverter data were additionally implemented. 

BUGFIX:

  • Exchange sonnenModule 3 by sonnenModule 4: After exchanging sonnenModule 3 by sonnenModule 4, in some cases, the storage system did not recognize the new battery module correctly. This resulted in the system not starting correctly after the exchange. This procedure has now been improved.
  • Cascaded systems: Some improvements have been made to stabilize the operation of cascaded systems. One enhancement is a more sensitive trickle charge behavior for the primary and all secondaries.  
  • Dashboard 2.0: In previous versions, the backup buffer was displayed twice. This has now been corrected. 

Software version: 1.7.10

Release date: November 7th, 2022 – only for new installations except in the USA, and all existing fleet of sonnenBatterie 10 performance in combination with sonnenProtect 8000
Status: Stable

FEATURE:

  • Adaption of lower and higher power limits for full charge requests for better operation of inverter and system. The new limit can be overwritten by the VPP in case more power is required.
  • The new power meter EM357 from Phoenix is integrated and compatible with software version 1.7.10 onwards. There is no change in any functionality for the systems with a phoenix meter compared with the previous Gavazzi meter.
  • For hybrid systems in Ireland and Italy, the minimum inverter firmware is set as 2.45. This will help Italian installers to have proper self-test measurements and values. For installers in Ireland, it will also avoid time-out errors while selecting the grid code ‘Ireland’.

BUGFIX:

  • Overload and microgrid functionality with sonnenBatterie 10 performance and sonnenProtect 8000 systems work normally again.
  • Eliminating Hybrid 9.53 systems going into manual standby and causing SOC drops and F1 switch open.
  • When a cascade system was commissioned successfully and in normal operation, then all systems report the correct SOC on the dashboard, and it matches with the SOC on the battery page.

Software version: 1.7.7

Release date: September 28th, 2022
Status: Stable

FEATURE:

  • API V1 will no longer be available for customers as API V1 will be replaced by API V2 which is more secure and improved. The sonnenSmart-Plugs will no longer be supported.
  • Rest Module 1 (This module implements basic user authentication using the HTTP Basic authentication provider.) API calls from spree scripts are no longer available and now they are replaced with MQTT (publish/subscribe protocol that allows edge-of-network devices to publish to a broker.)
  • Smarthome users can now have the same functionality with Rest Module 2 that they have with Rest Module 1. This will support the sonnenHeater after Rest Module 1 shut down.
  • In cascade systems, Primary and Secondary systems will have the same backup-buffer level.

BUGFIX:

  • In sonnenBatterie10 performance with 10 module systems which caused several restarts is now fixed which eliminates the dropping of the state of charge.
  • Error during start-up of systems with sonnenModule 2500 (LFP 2) has been fixed
  • Multiple Internal controller initializations and restarts lead to State of charge drops which have now been fixed
  • sonnenBatterie Hybrid 9.53 systems going into manual standby and causing SOC drops and F1 switch open has been fixed
  • sonnenModule 3 getting stuck at 10% State of charge after a full discharge was detected and has been fixed.
  • 5A current limit is now set per battery module string for sonnenModule 3 modules to allow 100% SOC charge within 24 hours.
  • Cascade systems now work without losing pairing between Primary and Secondary systems
  • In the cascade systems, Primary will get the correct inverter maximum power rating based on the real number of stacked modules.

Software version: 1.7.2

Release date: July 6th, 2022
Status: Stable

  • FEATURE: sonnenModule 4: Automatic update of all modules in the field to Firmware version 3.2.0 to be independent of different module configurations.
  • BUGFIX: Hybrid systems: Enable black start functionality with the newest software version & correct of black start functionality for systems with low SOC.
  • BUGFIX: Commissioning Assistant: Change requests for the PV reduction test during commissioning to increase robustness.
  • BUGFIX: Commissioning Assistant UK: Adaptation of the frequency calculation in the grid code UK-G99.
  • BUGFIX: Self consumption relay: Correction applied to hold minimum switch-on duration.
  • BUGFIX: Avoid error during start-up of systems with LFP1 & 2.

Software version: 1.6.24

Release date: April 29th, 2022
Status: Stable  

  • FEATURE: Time of Use (ToU): Interface established. From this software version on the ToU schedule can be sent to portals. Implementation of ToU modification in app pending.
  • FEATURE: Hybrid systems: The SOC limit for updates was raised from 5% to 10% to avoid errors when the system is running down to 4% SOC while updating.
  • BUGFIX: sonnenBatterie 10 performance: Inverter errors are reported to prevent possible deep discharge states.
  • BUGFIX: sonnenModule 4: Bug fixed that was causing false error messages.
  • BUGFIX: Manual charge/discharge during self-consumption did not stop automatically for some systems. Now, this got fixed with a default stop after 30 seconds for all systems.
  • BUGFIX: Cascade: The IP configuration is now changed automatically if a system gets another IP address.
  • BUGFIX: Hybrid systems: Backup buffer hysteresis is now followed correctly while charging.
  • BUGFIX: Commissioning Assistant: Information regarding reduction level 3 was corrected and PV reduction testing level 1 and 2 descriptions and calculations were updated.
  • BUGFIX: UK: Avoid an error in setting P(f)values on grid code UK-G99.
  • BUGFIX: Improvement of the Inverter FW Update of sB10p
  • BUGFIX: Malfunctioning of PV power reduction leading to temporal constant power limitation was resolved.

Software version: 1.6.18

Release date: March 22nd, 2022
Status: Stable

  • FEATURE: If the feed-in limit is set to 100 %, then the function "weather forecast" is not displayed in the Dashboard. For systems that do not have a feed-in limit the function of intelligent charging management is not needed and therefore also weather forecast is not needed.
  • FEATURE: Additional error message and a red Eclipse if a single sonnenModule 4 is not connected correctly in a sonnenBatterie 10.
  • FEATURE: In the Cascade operation we have renamed to units from Master and Slave to Primary and Secondary.
  • FEATURE: For Austria it is now possible to activate a different variant of P(U) in the Commissioning Assistant.
  • FEATURE: During a grid outage the battery system is still recording measurement values and events which have occurred, but these values are not sent to the server. Once the grid is available, the recorded values and events are uploaded to the server so that the data is available on the portal and the app.
  • FEATURE: Additional grid codes Belgium, Northern Ireland and Spain - RD 1699 have been added to the sonnenBatterie 10.
  • BUGFIX: Manual standby can now be activated and deactivated via the dashboard for sonnenModule 4.
  • BUGFIX: Hybrid battery systems with 3 or 4 units of battery module 2 kWh resp. sonnenModule 2500 no longer have discharging power limited to 3080W.
  • BUGFIX: For sonnenBatterie 10 systems with sonnenModule 4 in Italy the selftest procedure was improved.

Software version: 1.6.10

Release date: September 28th, 2021
Status: Stable

  • FEATURE: sonnenModule 3: A full charge for battery maintenance is now started already after 15 consecutive days without reaching 100% SOC (before 30 days). This improves battery health and helps prepare for the next winter season. 
  • FEATURE: sonnenBatterie 10 or sonnenBatterie 10 performance: If the system is already delivered with this software version, then there was an additional check in production to ensure that the initial password is programmed correctly. 
  • FEATURE: Italy: The documents needed for the Italian selftest have now been adapted to the current requirements.
  • FEATURE: Germany: For the VDE AR N 4105 in some cases it is meanwhile necessary to adjust values for the P(f) control. Now there are more possibilities for adjustments in the Commissioning Assistant.
  • BUGFIX: Internet connection: After a backup situation some systems only established the internet connection again the next day. Now the Internet connection is re-established immediately after the grid returns.
  • BUGFIX: Eclipse: It was solved that the Eclipse sometimes remained on orange although the internet connection was available again.
  • BUGFIX: Dashboard: Sometimes wrong energy flow values in offgrid mode have been displayed.
  • BUGFIX: Dashboard: In former software versions some systems showed UTC (Coordinated Universal Time) instead of local time.
  • BUGFIX: Backup mode: No more software updates are carried out during off-grid operation. In previous versions, an update in this state could lead to a system shutdown.
  • BUGFIX: sonnenModule 3: A bug has been fixed that blocked in some cases the full charge for battery maintenance.   
  • BUGFIX: sonnenModule 4: Improved software update process. In the former version not all firmware updates could be executed successfully. Now sonnenModule 4 recovers itself after a failed software update.

Software version: 1.6.0

Release date: April 1st, 2021
Status: Stable

  • FEATURE: sonnenBatterie 10 performance: More purposeful user communication in the Commissioning Assistent when selecting the Austrian grid code.
  • FEATURE: sonnenBatterie with display: An automatic update from display version V1 to version V3 is carried out. Additionally, improved wording to guide through the necessary calibration process after the update. 
  • FEATURE: Dashboard: The sonnenProtect 4000 and sonnenProtect 8000 have been added as a function block to the Dashboard of the system. 
  • FEATURE:  Module individual data for sonnenModule 2500 now visible in the dashboard. 
  • FEATURE: sonnenBatterie 10 performance: The hysteresis for switching the internal fan on and off has been improved. As a result, the fan starts less frequently. 
  • FEATURE: sonnenBatterie with display V3: The display has been redesigned. In addition to a dynamic status bar and a live screen with the current energy flows, many settings can be made directly on the display, such as setting the backup power buffer, language and display brightness. Official upgrade to the new display will take place on December 15, 2020. 
  • FEATURE: sonnenBatterie 10: Grid Codes for Europe (EN 50438), Ireland, Belgium and Spain now available during commissioning. 
  • FEATURE: sonnenBatterie 8 or higher: Improvement of the off-grid behaviour for “total grid drop” and “frequency drops/ frequency spikes”. These improvements will lead to faster reconnection times. 
  • FEATURE: sonnenModule 3: If the module temperature is below 10°C the charge and discharge current is limited to 5A. This avoids that the sonnenModule 3 could go into critical error mode and shuts down under this circumstances.
  • BUGFIX: sonnenBatterie 10 performance: After a change of the selected grid code now a restart of the unit is executed to assure that the inverter has taken over the new grid parameters. Improved that continually grid parameter settings for VDE AR 4105 are send to the inverter.  
  • BUGFIX: Cascade: In some cases it was not possible to configure a cascade of several sonnenBatteries in the Commissioning Assistant. Number of maximum cascade members in the system is now correct and so cascades can be configured correctly. 
  • BUGFIX: sonnenModule 3: Solved an issue that the serial number of the sonnenModule 3 was not shown in the Dashboard. 
  • BUGFIX: sonnenBatterie hybrid: Previously, some systems could incorrectly limit the maximum charging power to 1200W in certain operating conditions. 
  • BUGFIX: Time of Use: UTC (Universal Time Coordinated) was previously used as the internal system time for this function. This led to problems in the Time of Use function because UTC does not support daylight saving time (DST). Therefore, activating and deactivating battery charging was previously shifted by one hour during DST season. 
  • BUGFIX: sonnenBatterie 10 performance did not show the correct eclipse color after a startup of the sB10p without internet connection. We now show the correct eclipse state, based on a faster detection of missing internet connection.  
  • BUGFIX: sonnenProtect 4000 & 8000: In some cases, the LED which indicates overload conditions in offgrid mode remains on after pushing the protect button and bringing the sonnenProtect back in service.  We now show the correct indication of overload condition by sonnenProtect-LED.  
  • BUGFIX: sonnenModule 3 and sonnenModule 4: There were a few systems that did not perform the mandatory full charge every 30 days. This has now been fixed.
  • BUGFIX: Commissioning Assistant: Login problems in the commissioning assistant solved, as now the Commissioning Assistant will only be available, once the API is ready.  
  • BUGFIX: Commissioning Assistant: More than 6 measurement channels led to wrong measurement data transmission. Therefore, the max. amount of measurement channels which can be activated has been limited to 6 channels. (=max. 3 power meters) 
  • BUGFIX: sonnenBatterie 8 or higher:  We have fixed sending internally incomplete data measurements by an improved system performance. Systems are running now more stable. 

Software version: 1.5.5

Release date: November 24th, 2020
Status: Stable

  • FEATURE: Commissioning Assistant: Improvement of the display with example graphics when setting the country-specific inverter settings.
  • FEATURE: Release of firmware revision 2.25 for sonnenBatterie hybrid 9.53 due to certifications for Italy. 
  • BUG: sonnenBatterie 10 performance: Minor bug fixes when activating the microgrid through the sonnenProtect 8000.
  • BUG: sonnenBatterie 10: In some systems with up to 10 battery modules, there were problems with reading out the system data of the sonnenModules 4.